Online UPS
DX890-Series
DX890-Series Features
Online double conversion with full DSP control technology
IGBT inverter with output isolation transformer
100% Unbalance load capability
Output Power factor 0.9
Generator compatible
Support battery Cold start auto -restart when mains power is restored
ECO mode operation for energy saving
Superior protection
Surge
Short-Circuit
Over Voltage
Under Voltage
Over Charge
Reverse battery protection etc
5.7 inches LCD Touch screen, Friendly Human and Machine interface
Front Access make maintenance and replacement simplified (60~120 KVA)
Intelligent self-diagnosing function, all kinds of failure protection, Large capability of history records storage
High MTBF (> 2000o h) , Low MTTR (<0.5 h)
Standard emergency power Off (EPO)
Standard RS232, RS485 , dry contacts communication port
Optional SNMP communication port
Optional N+X redundancy parallel upto 6 units
HOptional input filter to improve input power factor
| MODEL | DX8910 | DX8915 | DX8920 | DX8930 | DX8940 | DX8960 | DX8980 | DX89100 | DX89120 | |
|---|---|---|---|---|---|---|---|---|---|---|
| Rating Capacity | 10KVA/9kW | 15KVA/13.5kW | 20KVA/18kW | 30KVA/27kW | 40KVA/36kW | 60KVA/54kW | 80KVA/72kW | 100KVA/90kW | 120KVA/108kW | |
| Input | ||||||||||
| Input wiring | 3-Phase 5-Wire (3ϕ+N+PE) | |||||||||
| Rated Voltage | 380/400/415 VAC | |||||||||
| Voltage Range | 285 ~ 475 VAC | |||||||||
| Rated Frequency | 50Hz/60Hz | |||||||||
| Frequency Range | 50Hz/60Hz ±5Hz | |||||||||
| Power Factor | ≥0.95 (with Filter) | |||||||||
| Delayed Start of rectifier | 10s (1~300 Settable) | |||||||||
| Bypass Voltage Range | ±20% (Settable) | |||||||||
| Output | ||||||||||
| Output Wiring | 3-Phase 5-Wire (3ϕ+N+PE) | |||||||||
| Rated Voltage | 380/400/415 VAC | |||||||||
| Output Voltage Regulation | ±1% | |||||||||
| Output Frequency Regulation | 50Hz/60Hz ±0.1% in battery mode | |||||||||
| Waveform | Sinusoidal | |||||||||
| Power Factor | 0.9 | |||||||||
| THDv | ≤1%(Linear Load); ≤5% (Non-Linear Load) | |||||||||
| Crest Factor | 3:1 | |||||||||
| Overload | 105% | |
|
|
|
|
|
|
|
| |
| Battery | ||||||||||
| DC Voltage | Lead Acid Battery: 360 VDC Lithium ironphosphate battery: 384 VDC | |||||||||
| No.of Batteries | Lead Acid Battery:12V x 30 pcs (support 28~32 pcs) Lead Acid Battery: 2V x 180 pcs (support 168~1922 pcs) Lithium ironphosphate battery:3.2V x 120 pcs (support 112~120 pcs) | |||||||||
| Charging Current | Charging rate (settable) x battery capacity (settable) number of battery groups (settable) | |||||||||
| System | ||||||||||
| Efficiency | In Line mode: Max. 93%; ECO mode: ≥98% | |||||||||
| Max No.of Parallel connections | 6 | |||||||||
| Protections | Shor-Circuit, Overload, Over Temp, Battery Low Voltage, Under Voltage, Over Voltage and Fan Failure Protection | |||||||||
| Communications | Standard Communications: RS232,RS485,CAN,NET,SNMP,dry contacts, and EPO | |||||||||
| EMI | EN62040-2 | |||||||||
| EMS | IEC61000-4-2 (ESD) IEC61000-4-3 (RS) IEC61000-4-4 (EFT) IEC61000-4-5 (Surge) | |||||||||
| Environmental | ||||||||||
| Operating Temperature | 0℃ ~ 40℃ | |||||||||
| Storage Temperature | -25℃ ~ +55℃ (without Battery) | |||||||||
| Relative Humidity | 0% ~ 95% (Non-condensing) | |||||||||
| Altitude | ≤1000m, derating 1% for each additional 100m | |||||||||
| Protection Level | IP 20 | |||||||||
| Noise | ≤65 dB (at 1m) | |||||||||
| Others | ||||||||||
| Cabinet Dimensions (WxDxH)mm | 400x800x1100 | 600x700x1500 | 700x800x700 | |||||||
| Packaged Dimensions (WxDxH)mm | 490x920x1300 | 700x800x1650 | 800x900x1850 | |||||||
| Net Weight(kg) | 158 | 165 | 175 | 210 | 260 | 460 | 590 | 630 | 690 | |
| Net Weight(kg) | 200 | 207 | 217 | 252 | 302 | 480 | 620 | 660 | 720 | |
| Color | Black |