DX660-Series Features

  • Advanced DSP control and 3-Level technology. VFI Comfortable

  • Output power factor 1.0

  • Active Power factor correction (APFC), input power factor upto 0.99

  • High efficiency 95% (up to 98% in ECO mode)

  • Advanced digital parallel technology

  • Wide input range(110 ~ 288 VAC) and frequency range (40 ~ 70 Hz)

  • 50Hz / 60Hz frequency auto sensing

  • Two modes of frequency conversion: 50Hz input / 60Hz output or 60Hz input / 50Hz output | ECO mode

  • Dual inout design, supporting independent bypass

  • Flexible battery configuration (settable 10-20 pcs batteries)

  • Digitally controlled charger

  • High charging current available (Max.12A)

  • Charging voltage and current configurted by demands

  • Linear derating in low voltage input reducing battery discharging times, extending the service life of battery

  • Intelligent battery management, automatic floating / equalizing charge control, charger dormancy control, increasing battery life by 50%

  • Ability to switch on the UPS with batteries

  • Settable delayed start time when mains power is restored, reducing the impact on power grid or generator

  • Fan speed varies intelligently with temperature, reducing noise and extending its service life

  • Equipped with self-aging function

  • Compact internal layout, miniaturized the complete unit for small footprint

  • LCD+LED display, multi functional keys operation, friendly human-machine interface

  • Powerful bachground software for parameters configuration

  • Advanced multi-platform communications: RS232, USB, RS485, SNMP and dry contacts communication interfaces

  • Effective Software and Hardware protection function, robust self-diagnostic function, and abundant event log for check

  • Availabe RS232 and Smart-Card slot included, Optional Parallel function, battery temperature compensation, SNMP card, USB, RS485 card, dry contacts, EMD, and SMS alarms


MODEL DX906 DX9010
Rating Capacity 6KVA/6kW 10KVA/10kW
Input
Input wiring Single-Phase 3-Wire (1ϕ+N+PE)
Rated Voltage 208/220/230/240 VAC
Voltage Range 110~176 VAC (linear derating between 50% and 100% load);, 176~288 VAC)(No derating)
Rated Frequency 50Hz/60Hz (auto-sensing)
Frequency Range 40Hz~70Hz
Power Factor ≥0.99
THDi ≤5%
Bypass input Voltage Range -40%~+15% (Settable)
Output
Output Wiring Single-Phase 3-Wire (1ϕ+N+PE)
Rated Voltage 208(PF=0.9)/220/230/240 VAC
Voltage Regulation Accuracy ±1%
Frequency Accuracy Synchronized to bypass in mains mode;50Hz/60Hz ±0.1% in battery mode
Waveform Sinusoidal
Output Power Factor 1
THDv ≤1%(Linear Load); ≤4% (Non-Linear Load)
Crest Factor 3:1
Overload 105%
Battery
DC Voltage 120 VDC(120 ~ 240 VDC Variable)
No.of Battery 10 pcs(10 ~ 20 settable)
In-built Battery (Standard Model) 12V/7AH x 10 12V/9AH x 10
Charging Current Standard Model: 1A; Long time Model: 5A (default), 1A~5A settable, 12A optional
Recharge Time Standard Model: 90% capacity restored in 8 Hours; Long-Time Model: depend on the capacity of battery
System
Max Efficeincy ≥94% at 100% Load, Max. 95% at 60% Load, ≥98% in ECO mode
Transfer time 0 ms
Max No.of Parallel connections 4
Protections Shor-Circuit, Overload, Over Temp, Battery Low Voltage, Under Voltage, Over Voltage and Fan Failure Protection
Communications Standard Communications: RS232/USB/RS485/SNMP/battery temperature compensation(optional)
Optional Configurations: Wi-Fi card, Parallel Port, LBS Port, GPRS card, Battery Temperature sensor, EMD and SMS alarms
Display LCD + LED screen
Environmental
Operating Temperature 0℃ ~ 40℃
Storage Temperature -25℃ ~ +55℃ (without Battery)
Relative Humidity 0% ~ 95% (Non-condensing)
Altitude ≤1000m, derating 1% for each additional 100m
Protection Level IP 20
Noise ≤55dB (at 1m) ≤58dB (at 1m)
Others
Cabinet Dimensions (WxDxH)mm 191x465x711(S), 191x465x350(H) 191x465x711(S), 191x465x350(H)
Packaged Dimensions (W x D x H) (mm) 310x654x941(S), 318x595x475(H) 310x685x941(S), 318x617x475(H)
Net Weight(kg) 53(S), 14.5(H) 62(S), 16.5(H)
Gross Weight(kg) 61(S), 16(H) 70(S), 18(H)
Color Black