Online UPS
DX890-Series
DX890-80k-500k Series Features
Online double conversion with full DSP control technology
Latest IGBT rectifier technology,High input power factor(>0.99) and low THDi(≤3%)
High Efficiency even at light loads
Strong mixed load capacity and high overload capacity
Compact and small footprint
unique ventilation design
Batteries are directly connected directly to the bus, improving the impact resistance of UPS output
Output isolation transformer using DZn0 winding makes strong capability with unbalanced loads
input and output are completely isolated for great security
Simulated modular design makes maintanance rasy and quick
High MTBF (> 20000 h) , Low MTTR (<0.5 h)
Front accessible maintanance and installation against wall allowed
Bottom and sides cable entry compatible
Generator compatible
Intelligent self-diagnosing function, superior failure protection, large capability of history records storage
Optional N+X redundancy parallel upto 6 units
MODEL | DX8980 | DX89100 | DX89120 | DX89160 | DX89200 | DX89250 | DX89300 | DX89400 | DX89500 | |
---|---|---|---|---|---|---|---|---|---|---|
Rating Capacity | 80KVA/72kW | 100KVA/90kW | 120KVA/108kW | 160KVA/144kW | 200KVA/180kW | 250KVA/225kW | 300KVA/270kW | 400KVA/360kW | 500KVA/450kW | |
Input | ||||||||||
Input wiring | 3-Phase 5-Wire (3ϕ+N+PE) | |||||||||
Rated Voltage | 380/400/415 VAC | |||||||||
Voltage Range | 304 ~ 346V (derating 10%), 346 ~ 456 V (full load) | |||||||||
Rated Frequency | 50Hz/60Hz | |||||||||
Frequency Range | 50Hz/60Hz ±5Hz | |||||||||
Power Factor | ≥0.99 (with Filter) | |||||||||
Total harmonic distortion (THDi) | ≤3% | |||||||||
Delayed Start of rectifier | 10s (1~300 Settable) | |||||||||
Bypass Voltage Range | ±20% (Settable) | |||||||||
Output | ||||||||||
Output Wiring | 3-Phase 5-Wire (3ϕ+N+PE) | |||||||||
Rated Voltage | 380/400/415 VAC | |||||||||
Output Voltage Regulation | ±1% | |||||||||
Output Frequency Regulation | 50Hz/60Hz ±0.1% in battery mode | |||||||||
Waveform | Sinusoidal | |||||||||
Power Factor | 0.9 | |||||||||
Voltage distortion (THDv) | ≤2%(Linear Load); ≤5% (Non-Linear Load) | |||||||||
Crest Factor | 3:1 | |||||||||
Overload | 105% |
|
|
|
|
|
|
|
| |
Battery | ||||||||||
DC Voltage | Lead Acid Battery: 600 VDC Lithium ironphosphate battery: 614.4 VDC | |||||||||
No.of Batteries | Lead Acid Battery:12V x 50 pcs (support 48~52 pcs) Lead Acid Battery: 2V x 300 pcs (support 288~312 pcs) Lithium ironphosphate battery:3.2V x 192 pcs (support 192~208 pcs) | |||||||||
Charging Current | Charging rate (settable) x battery capacity (settable) number of battery groups (settable) | |||||||||
System | ||||||||||
Efficiency | Line mode: Max. 92%; ECO mode: ≥97% | Line mode: Max. 94%; ECO mode: ≥98% | ||||||||
Max No.of Parallel connections | 6 | |||||||||
Protections | Shor-Circuit, Overload, Over Temp, Battery Low Voltage, Under Voltage, Over Voltage and Fan Failure Protection | |||||||||
Communications | Standard Communications: RS232,RS485,CAN,NET,SNMP,dry contacts, and SMS alarms | |||||||||
Display | Standard Communications: RS232,R5.7 inches LCD touch screen | |||||||||
Environmental | ||||||||||
Operating Temperature | 0℃ ~ 40℃ | |||||||||
Storage Temperature | -25℃ ~ +55℃ (without Battery) | |||||||||
Relative Humidity | 0% ~ 95% (Non-condensing) | |||||||||
Altitude | ≤1000m, derating 1% for each additional 100m | |||||||||
Protection Level | IP 20 | |||||||||
Noise | ≤65 dB (at 1m) | |||||||||
Others | ||||||||||
Cabinet Dimensions (WxDxH)mm | 800x800x1800 | 800x860x1700 | 1210x860x1950 | 2380x860x1950 | ||||||
Packaged Dimensions (WxDxH)mm | 900x900x2050 | 900x1000x1950 | 1300x1000x2200 | 1300x1000x2200 | ||||||
Net Weight(kg) | 580 | 630 | 680 | 790 | 1135 | 1275 | 1355 | 2090 | 2300 | |
Net Weight(kg) | 630 | 680 | 730 | 840 | 1200 | 1340 | 1420 | 2200 | 2410 | |
Color | Black |