DOU Series DOU-1k~10k Features

  • DSP Based Design

  • Suitable for all kinds of loads (resistive, inductive and non-linear loads etc)

  • High over load capability (upto 150%)

  • Bypass dual DSP control design to enhance more reliability

  • Supports dual input, hot standby in series

  • Redundant & parallelable with advance parallel current-sharing control technology

  • Cold Start and Mains Starts function

  • Generator Compatible

  • High charging capability

  • Configuration with output isolation transformer

  • Superior Protection:

    • Surge

    • Over Voltage

    • Under Voltage

    • Over Charge

    • Over Load

    • Reverse Battery

    • Short-Circuit

  • Advanced Communications:

    • RS232

    • USB ports

    • SNMP

    • dry contacts

    • Over Load

    • RS485

  • Generator Compatible

  • MStatic bypass switch available, Manual Bypass Optional


MODEL DOU1K DOU2K DOU3K DOU5K DOU6K DOU10K
Capacity) 1KVA/KW 2KVA/KW 3KVA/KW 5KVA/KW 6KVA/KW 10KVA/KW
Nominal Voltage 220/230/240 VAC (1ph+N+PE, 3 Wire)
AC Input
Operating Voltage Range 110V~300V AC @50% Load/ 140V ~300VAC @ Full Load
Frequency 50/60Hz ±10% (Auto Sensing)
Power Factor 0.99
output Voltage / Power factor 220/230/240 VAC / ±1% / 1 unit Pf
Output frequency auto sensing 50/60Hz ±1~10% sync mode(configurable), 50/60 Hz ±1Hz Battery mode
Harmonic distortion (THDv) ≤2% (linear load); ≤5% (n0n-linear load)
Crest Factor 3:1
Efficiency Upto 94% Dual Conversion Mode, 99% ECO Mode
Battery
DC Voltage 36V 48V 72V 96V 72V 96V
Charger 6.5~13A Configurable
Typical Recharge Time 8-12 Hours (90& of full capacity)
System Features
LCD Indications Input Voltage/Frequency, Output Voltage/Frequency, Battery Voltage, Load Watt/VA and %, Inverter Temperature, Operation mode such as `Online`, `ON Bat`, or On `Bypass~, Fault codes, Battery & Load Bar graph, Input Current, Output Current, Battery current
LED Indications Normal Operation, Bypass, Abnormal, Fault and Battery Mode
Alarms/Protections Batt, Low, DC High, Inverter Under/Over Voltage, UPS over load, Short Circuit, Fan Failure and UPS fault, Transient surge, Input and output fuse
Over load Capacity ≤125% for 10 min, >125~150 % for 1 min, >150% for 200ms
Transfer Time ≤AC to BAttery: 0ms, Inverter to Bypass: 4ms (Typical)
Environmental
Operating Temperature 0℃ ~ 45℃
Storage Temperature 10℃ ~ 55℃
Humidity/Altitutde 0% ~ 95% RH / <1500M
Noise / Cooling <55Db / Forced air cooling
Physical
Dimesions (WxDxH) mm 144x400x215 192x469x399 220x481x438
Net Weight (kg) 6 10.7 11.2 17 18 20
Standards
Quality ISO 9001:2015, ISO 140001:2015, BIS
Safety/ IP Rating IEC/EN62040-1/IP20/IP21
EMC/Performance IEC/EN62040-2,IEC/EN62040-3 Complying to CE
Communication Interface
Standard RS-232
Optional SNMP/ModBus/Dry Contact/USB/RS-485
Monitoring Software Net Agent utility v5.8/UPSilon 2000